18/30(36)kV XLPE Insulated PVC Sheathed Unarmoured Power Cable

Single Core (Unarmoured )

Conductor
Conductor
screen

( mm )
Insulation
thickness

( mm )
Insulation
screen

( mm )
Copper
screen
tape
( mm )
Sheath
thickness

( mm )
Overall
diameter
approx.
( mm )
Cable
weight
approx.
( kg/km )
Insulation
resistance at
15.6°C (Min.)
( Mohm/km)
Size

( mm2 )
Shape

Outside
diameter
( mm )

50
70
95
120
150

C.C.
C.C.
C.C.
C.C.
C.C.

8.05
9.67
11.39
12.33
14.24

0.8
0.8
0.8
0.8
0.8

8.0
8.0
8.0
8.0
8.0

1.0
1.0
1.0
1.0
1.0

0.1
0.1
0.1
0.1
0.1

2.0
2.1
2.1
2.2
2.2

35.0
36.8
38.6
40.2
41.7

1519
1799
2133
2424
2767

2550
2300
2100
2000
1850

185
240
300
400
500

C.C.
C.C.
C.C.
C.C.
C.C.

15.98
18.32
20.65
23.33
26.34

0.8
0.8
0.8
0.8
0.8

8.0
8.0
8.0
8.0
8.0

1.0
1.0
1.0
1.0
1.0

0.1
0.1
0.1
0.1
0.1

2.3
2.4
2.4
2.5
2.7

43.6
46.3
48.8
51.7
55.0

3206
3881
4579
5511
6619

1700
1600
1450
1300
1200

3 Core (Unarmoured )

Conductor
Conductor
screen

( mm )
Insulation
thickness

( mm )
Insulation
screen

( mm )
Copper
screen
tape
( mm )
Sheath
thickness

( mm )
Overall
diameter
approx.
( mm )
Cable
weight
approx.
( kg/km )
Insulation
resistance at
15.6°C (Min.)
( Mohm/km)
Size

( mm2 )
Shape

Outside
diameter
( mm )

50
70
95
120
150

C.C.
C.C.
C.C.
C.C.
C.C.

8.05
9.67
11.39
12.33
14.24

0.8
0.8
0.8
0.8
0.8

8.0
8.0
8.0
8.0
8.0

1.0
1.0
1.0
1.0
1.0

0.1
0.1
0.1
0.1
0.1

3.2
3.3
3.5
3.6
3.7

73.7
77.4
81.4
84.8
88.1

5234
6152
7246
8249
9316

2500
2300
2100
2000
1850

185
240
300

C.C.
C.C.
C.C.

15.98
18.32
20.65

0.8
0.8
0.8

8.0
8.0
8.0

1.0
1.0
1.0

0.1
0.1
0.1

3.9
4.1
4.2

92.1
98.0
103.4

10739
12928
15191

1700
1600
1450

3 Core (Steel Wire Armoured)

Conductor
Insulation
thickness

( mm )
Copper
screen
tape
( mm )
Inner
sheath
thickness
( mm )
Armour
wire
diameter
( mm )
Outer
sheath
thickness
( mm )
Overall
diameter
approx.
( mm )
Cable
weight
approx.
( kg/km )
Insulation
resistance at
15.6°C (Min.)
( Mohm/km)
Size

( mm2 )
Shape

Outside
diameter
( mm )

50
70
95
120
150

C.C.
C.C.
C.C.
C.C.
C.C.

8.05
9.67
11.39
12.33
14.24

8.0
8.0
8.0
8.0
8.0

0.1
0.1
0.1
0.1
0.1

1.6
1.8
1.8
1.8
1.8

2.5
3.15
3.15
3.15
3.15

3.4
3.4
3.5
3.6
3.7

79
84
88
91
95

8840
10860
12170
13400
14800

2550
2300
2100
2000
1850

3 Core (Steel Tape Armoured)

Conductor
Insulation
thickness

( mm )
Copper
screen
tape
( mm )
Inner
sheath
thickness
( mm )
Armour
tape
diameter
( mm )
Outer
sheath
thickness
( mm )
Overall
diameter
approx.
( mm )
Cable
weight
approx.
( kg/km )
Insulation
resistance at
15.6°C (Min.)
( Mohm/km)
Size

( mm2 )
Shape

Outside
diameter
( mm )

50
70
95
120
150

C.C.
C.C.
C.C.
C.C.
C.C.

8.05
9.67
11.39
12.33
14.24

8.0
8.0
8.0
8.0
8.0

0.1
0.1
0.1
0.1
0.1

1.6
1.8
1.8
1.8
1.8

0.5
0.5
0.8
0.8
0.8

3.2
3.3
3.4
3.6
3.7

77
81
84
89
93

6900
7930
9060
11300
12500

2550
2300
2100
2000
1850

website: www.caledonian-cables.com

email: sales@caledonian-cables.com

 

* C.C.: Stranded and compacted circular.